SunScan SunSleeve 22mm R1 Pipe Insulation

Price
Regular price
Regular price R 16300 Sale price
Save R 42.05
R 105.17 excl. VAT
/
Tax included. Shipping calculated at checkout.
  • Available - Ready to order
  • Backordered, shipping soon
  • Secure online payments
  • We deliver across Africa

SunScan’s SunSleeve thermal pipe insulation has been designed for the plumbing and gas industries. It offers a well-insulated, value-for-money solution that is well suited to the South African market.

Application

Thermal insulation for plumbing and gas pipe work.

Dimensions

  • Ø 21mm x 2000mm x Ø 15mm Tube
  • Ø 22mm x 2000mm x Ø 22mm Tube

Technical Properties

Property Value Standard
Thermal conductivity factor at average temperature -20°C <0.031 W/(m.k) GB/T10294
Thermal conductivity factor at average temperature 0°C <0.034 W/(m.k) GB/T10294
Thermal conductivity factor at average temperature 40°C <0.036 W/(m.k) GB/T10294
Water vapour permeability resistance factor μ coefficient <2.8 × 10-11 g/(m.s.pa) GB/T17146-1997
Water vapour permeability resistance factor >7.0 × 103 GB/T17146-1997
Density <95 kg/m³ GB/T6343
Flammability - Oxygen index >32% GB/T2406
Flammability - SDR <75 GB/T8627
Behaviour Self-extinguishing, non-dripping, no flame spread -

The R-value of insulation is a value that is used to measure how well a specific type of insulation can resist heat flow. The higher the R-value, the more effective the material is at preventing heat transfer. The R-value is calculated by dividing the insulation by its K-value.

K-Value: 0.036 W/mK at 40°C

*Equivalent Thickness (Meters)

R Value = *Equivalent Thickness
K Factor (W/mk)

*Equivalent Thickness = R2 × ln(R2/R1)

Where:
ln = Natural Log Function
R1 = inner radius of insulation (in)
R2 = outer radius of insulation (in)

R-VALUE (15 ID × 21 THK)

0.0285 × ln (0.0285 / 0.0075)
0.036 (W/mk)

R-value = 1.05681537664987

R-VALUE (22 ID × 22 THK)

0.033 × ln (0.033 / 0.011)
0.036 (W/mk)

R-value = 1.00700364684555

Compliance

SunScan SunSleeve Thermal Insulation conforms to SANS 10400-XA and has an R-value that exceeds the required R-1 value.

Installation Note

Insulation installed outside and exposed to weather must be coated with a suitable UV-resistant paint or covered with a slip cover to avoid or slow degradation.

Important:

All solar products, power systems, water heating and gas products and their components must be installed by appropriately qualified personnel. All installations must adhere to local wiring regulations and standards. Sustainable Online will not be held liable for any product malfunctions as a result of incorrectly installed systems.